Free Compressed Air Calculator

Compressed Air Pipe Sizing Calculator

Find the correct DN pipe size for your compressed air distribution run and verify pressure drop stays within limits.

Compressed Air Pipe Sizing Calculator

Enter flow, length and pressure to size the pipe.

Uses Rohrback approximation formula. Sizes: DN15, 20, 25, 32, 40, 50, 65, 80, 100. Target ≤ 0.1 bar drop for main rings.

Frequently Asked Questions

What is an acceptable pressure drop in a compressed air system?

The industry standard is a maximum 0.1 bar (10 kPa) pressure drop across the main distribution ring at full flow. For branch lines, an additional 0.1 bar is typically allowed. Total system pressure drop from compressor to point of use should not exceed 0.3 bar to avoid efficiency losses.

Why use a ring main for compressed air distribution?

A ring main (loop) feeds each outlet from two directions simultaneously, halving the effective pipe length and reducing pressure drop. It also provides redundancy — if one section is isolated for maintenance, supply is maintained from the other direction. Ring mains are recommended for most workshop and factory installations.

How do I convert L/min to CFM for compressed air?

1 CFM (cubic foot per minute) = 28.32 litres per minute. To convert L/min to CFM: divide by 28.32. For example, 300 L/min ÷ 28.32 = 10.6 CFM. The calculator shows both units in its results.